THERMO PRODUCTS,LLC. BOX 217 NORTH JUDSON, IN 46366 PHONE: (574) 896-2133 MG-807C E
All installations and services must be performed by qualified service personnel. 8 temperature stability. If the chimney is on the homes exterior and
All installations and services must be performed by qualified service personnel. 9 Piping from the natural gas meter to the furnace shall be in accord
All installations and services must be performed by qualified service personnel. 10 EXAMPLE: A line must supply a furnace of 110,000 BTU/hr input, a h
All installations and services must be performed by qualified service personnel. 11 - COPPER TUBING SIZE FOR LIQUIFIED PETROLEUM GASES - All
All installations and services must be performed by qualified service personnel. 12 TWO PIECE MOUNTING PLATE When mounting the burner, the upper mou
All installations and services must be performed by qualified service personnel. 13 to have the possibility of being carcinogenic to humans. IARC has
All installations and services must be performed by qualified service personnel. 14 Furnace Model Orifice Size
All installations and services must be performed by qualified service personnel. 15 In summary, setting the combustion air on the Thermo Pride Midco R
All installations and services must be performed by qualified service personnel. 16 EXAMPLE: Heating output of furnace is 100,000 x 1.4 ÷ 100 = 1400 C
All installations and services must be performed by qualified service personnel. 17 DUCT WORK/AIR CONDITIONING: If the furnace is used in connection
TABLE OF CONTENTS SECTION BEGINNING PAGE WARNING AND INSTRUCTION LABELS
All installations and services must be performed by qualified service personnel. 18 A. 400 CFM X 3 TON (36,000 BTU'S) = 1,200 CFM FOR COOLING
All installations and services must be performed by qualified service personnel. 19 N. FAN AND LIMIT POSITION AND LOCATION Power gas furnace models
All installations and services must be performed by qualified service personnel. 20 A. FAN & LIMIT LOCATION WITH H-COIL: The fan & limit cont
All installations and services must be performed by qualified service personnel. 21 All electrical wiring must be installed in strict accordance with
All installations and services must be performed by qualified service personnel. 22
All installations and services must be performed by qualified service personnel. 23
All installations and services must be performed by qualified service personnel. 24
All installations and services must be performed by qualified service personnel. 25
All installations and services must be performed by qualified service personnel. 26 Wiring: All electrical wiring must be installed in strict accorda
All installations and services must be performed by qualified service personnel. 27 II. STARTING THE UNIT A. INITIAL START UP: 1. Check all wiring f
All installations and services must be performed by qualified service personnel. 1 This page contains reproductions of the various warning and instru
All installations and services must be performed by qualified service personnel. 28 elevation of 2,000 feet or less, no reduction in input is required
All installations and services must be performed by qualified service personnel. 29 ORIFICE CHARTFURNACEMODEL NO.L.P. NAT.PGT5-100PGT11-125PGT16-160PG
All installations and services must be performed by qualified service personnel. 30 V. DEALER MAINTENANCE A. ELECTRICAL: 1. Check all wiring for loo
All installations and services must be performed by qualified service personnel. 31 Reassemble the furnace to its original construction. Remount the
All installations and services must be performed by qualified service personnel. 32 VII. REPLACEMENT PARTS
All installations and services must be performed by qualified service personnel. 33
All installations and services must be performed by qualified service personnel. 34
All installations and services must be performed by qualified service personnel. 35
All installations and services must be performed by qualified service personnel. 36
All installations and services must be performed by qualified service personnel. 2 This page contains various warnings and cautions reproduced from th
All installations and services must be performed by qualified service personnel. 3 I. GENERAL INSTRUCTIONS These instructions must be read in their e
All installations and services must be performed by qualified service personnel. 4 - MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS - MODEL NO. FROM SI
All installations and services must be performed by qualified service personnel. 5 EXAMPLE: 100,000 BTUH input furnaces requires "two" openi
All installations and services must be performed by qualified service personnel. 6 Trim or remove nearby trees that could interfere with chimney draf
All installations and services must be performed by qualified service personnel. 7 NOTE: If this furnace replaces an appliance with a vent that was o