1083292-UIM-A-0114When paired with aYork heat pumpMODULATING ECMRESIDENTIAL GAS FURNACESMODELS: TP9C, YP9C, CP9C, and LP9C Series(Up to 98% AFUE Mu
1083292-UIM-A-011410 Johnson Controls Unitary ProductsHorizontal FiltersAny branch duct (rectangular or round duct) attached to the plenummust attach
1083292-UIM-A-0114Johnson Controls Unitary Products 11GAS CONVERSION FOR PROPANE (LP)This furnace is constructed at the factory for natural gas-fired
1083292-UIM-A-011412 Johnson Controls Unitary ProductsAnnual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test pro
1083292-UIM-A-0114Johnson Controls Unitary Products 13CONTROL WIRINGThis furnace can be connected to the wall thermostat and outdoor A/Cor heat pump u
1083292-UIM-A-011414 Johnson Controls Unitary ProductsWhen connecting the Communicating Control (wall thermostat) and fur-nace control to a non-commun
1083292-UIM-A-0114Johnson Controls Unitary Products 15For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” do
1083292-UIM-A-011416 Johnson Controls Unitary Products FIGURE 23: Thermostat Chart - Two Stage Air Conditioner – Variable Speed Modulating FurnaceC24
1083292-UIM-A-0114Johnson Controls Unitary Products 17 FIGURE 24: Thermostat Chart - Two Stage Air Conditioner with Single Stage Thermostat – Variabl
1083292-UIM-A-011418 Johnson Controls Unitary Products FIGURE 25: Thermostat Chart - Single Stage Heat Pump – Variable Speed Modulating FurnaceC24 –
1083292-UIM-A-0114Johnson Controls Unitary Products 19 FIGURE 26: Thermostat Chart - Single Stage Heat Pump – Variable Speed Modulating FurnaceC24 –
1083292-UIM-A-01142 Johnson Controls Unitary ProductsThe York YP9C is part of a “Hybrid Comfort System” when paired with aYork Heat pump.These high ef
1083292-UIM-A-011420 Johnson Controls Unitary Products FIGURE 27: Thermostat Chart - Two Stage Heat Pump – Variable Speed Modulating FurnaceOReversin
1083292-UIM-A-0114Johnson Controls Unitary Products 21ACCESSORY CONNECTIONSThe furnace control will allow power-switching control of various acces-sor
1083292-UIM-A-011422 Johnson Controls Unitary ProductsThe condensate will flow to the drain better if an open stand pipe isinstalled in the drain line
1083292-UIM-A-0114Johnson Controls Unitary Products 23 FIGURE 29: Upflow ConfigurationINDUCER ROTATED FORLEFT SIDE VENTINGUPFLOWAS RECEIVEDINDUCER RO
1083292-UIM-A-011424 Johnson Controls Unitary Products FIGURE 30: Downflow ConfigurationAIRFLOWAIRFLOWMove raingutter hoseto this positionDOWNFLOW -
1083292-UIM-A-0114Johnson Controls Unitary Products 25 FIGURE 31: Horizontal Left ConfigurationHORIZONTAL - LEFTINDUCER ROTATEDHORIZONTAL - LEFTINDUC
1083292-UIM-A-011426 Johnson Controls Unitary Products FIGURE 32: Horizontal Right ConfigurationAIRFLOWHORIZONTAL - RIGHTINDUCER ROTATEDHORIZONTAL -
1083292-UIM-A-0114Johnson Controls Unitary Products 27SECTION VII: COMBUSTION AIR AND VENT SYSTEMCOMBUSTION AIR AND VENT SAFETYThis Category IV, dual
1083292-UIM-A-011428 Johnson Controls Unitary ProductsTable 7: Maximum Equivalent Pipe LengthElevation Sea level - 2000 Elevation 6001 - 7000Model Inp
1083292-UIM-A-0114Johnson Controls Unitary Products 29Dimensions are those required in Standard ASTM D-3311.Example:An 80,000 BTUH furnace requires 32
1083292-UIM-A-0114Johnson Controls Unitary Products 3• Furnaces for upflow installation on combustible flooring shall notbe installed directly on carp
1083292-UIM-A-011430 Johnson Controls Unitary ProductsVENT CLEARANCES† A vent shall not terminate directly above a sidewalk or paved driveway that is
1083292-UIM-A-0114Johnson Controls Unitary Products 31VENT SYSTEMThis furnace is certified to be installed with one of two possible ventconfigurations
1083292-UIM-A-011432 Johnson Controls Unitary Products DOWNWARD VENTINGIn some applications, it may be necessary to run the vent pipe and airintake do
1083292-UIM-A-0114Johnson Controls Unitary Products 33An unconfined space is not less than 50 ft3 (1.42 m3) per 1,000 BTU/hr (0.2928 kW) input rating
1083292-UIM-A-011434 Johnson Controls Unitary ProductsAir Supply Openings and Ducts1. An opening may be used in lieu of a duct to provide to provide t
1083292-UIM-A-0114Johnson Controls Unitary Products 35Specially Engineered InstallationsThe above requirements shall be permitted to be waived where s
1083292-UIM-A-011436 Johnson Controls Unitary ProductsVerify natural gas input rate by clocking meter.1. Turn off all other gas appliances and pilots.
1083292-UIM-A-0114Johnson Controls Unitary Products 37ADJUSTMENT OF MANIFOLD GAS PRESSUREInlet and manifold gas pressure may be measured by connecting
1083292-UIM-A-011438 Johnson Controls Unitary ProductsADJUSTMENT OF FAN CONTROL SETTINGSCooling - The airflow delivered by the furnace during cooling
1083292-UIM-A-0114Johnson Controls Unitary Products 39NOTE: All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed
1083292-UIM-A-01144 Johnson Controls Unitary ProductsINSPECTIONAs soon as a unit is received, it should be inspected for possible dam-age during trans
1083292-UIM-A-011440 Johnson Controls Unitary ProductsSECTION IX: SAFETY CONTROLSCONTROL CIRCUIT FUSEA 3-amp fuse is provided on the control circuit b
1083292-UIM-A-0114Johnson Controls Unitary Products 41TROUBLESHOOTINGThe following visual checks should be made before troubleshooting:1. Check to see
1083292-UIM-A-011442 Johnson Controls Unitary ProductsSECTION XI: REPLACEMENT PARTS LISTDESCRIPTIONMOTORMOTOR, DIRECT DRIVE BLOWERBLOWER, COMBUSTIONEL
1083292-UIM-A-0114Johnson Controls Unitary Products 43SECTION XII: WIRING DIAGRAM FIGURE 47: Wiring DiagramPOWER SUPPLY 115-1-60GAS VALVETO AIR CONDI
1083292-UIM-A-011444 Johnson Controls Unitary ProductsNOTES
1083292-UIM-A-0114Johnson Controls Unitary Products 45SECTION XIII: START UP SHEET33" 97% - 98% AFUE Modulating Gas Furnace Start Up Sheet Prope
Subject to change without notice. Published in U.S.A. 1083292-UIM-A-0114Copyright © 2014 by Johnson Controls, Inc. All rights reserved. Supersedes: 10
1083292-UIM-A-0114Johnson Controls Unitary Products 5SECTION II: DUCTWORKDUCTWORK GENERAL INFORMATIONThe duct system’s design and installation must:1.
1083292-UIM-A-01146 Johnson Controls Unitary ProductsRESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTIONReturn air may enter the furnace thro
1083292-UIM-A-0114Johnson Controls Unitary Products 7When moving or handling this furnace prior to installation it is recom-mended to leave the doors
1083292-UIM-A-01148 Johnson Controls Unitary ProductsFURNACE ASSEMBLY - MC SERIES COILS ONLYMC coils are supplied ready to be installed in a horizonta
1083292-UIM-A-0114Johnson Controls Unitary Products 9SECTION III: FILTERSFILTER INSTALLATIONAll applications require the use of a field installed filt