OUTDOOR COMBINATION OIL-FIRED
FURNACE AND AIR CONDITIONING UNIT
MODEL OPA
INSTALLATION AND SERVICE MANUAL
Please read these instructions prior to installation, initial firing, and before
performing any service or maintenance.
These instructions must be retained by the homeowner for future reference by
qualified heating contractor.
Thermo Products, LLC
PO Box 217
MO-424 North Judson, IN 46366
ECN 4650-MA Phone: (574) 896-2133 Made In USA
: If the information in this manual is not followed exactly, a
fire or explosion may result causing property damage, personal
injury, or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU FIND AN OIL LEAK:
Do not try to light any appliance.
Immediately call your oil supplier.
If you cannot reach your oil supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the oil supplier. (These entities are referred to in these instructions
as a qualified heating contractor).
Vue de la page 0
1 2 3 4 5 6 ... 90 91

Résumé du contenu

Page 1 - MODEL OPA

OUTDOOR COMBINATION OIL-FIRED FURNACE AND AIR CONDITIONING UNIT MODEL OPA INSTALLATION AND SERVICE MANUAL Please read these inst

Page 2

All installations and services must be performed by qualified service personnel. 9 II. GENERAL INSTRUCTIONS The entire text of these instructions m

Page 3

All installations and services must be performed by qualified service personnel. 10 A. Codes and Clearances: The following items must be considered

Page 4

All installations and services must be performed by qualified service personnel. 11 5. Table 1 lists the required minimum clearances to combustible

Page 5

All installations and services must be performed by qualified service personnel. 12 surfaces. This clearance helps to promote air circulation under

Page 6

All installations and services must be performed by qualified service personnel. 13 condenser coil area are maintained. These openings are not to be

Page 7

All installations and services must be performed by qualified service personnel. 14 In addition, long term exposure of building materials to combusti

Page 8

All installations and services must be performed by qualified service personnel. 15 Figure 3: Installation of a Condensate Drainage Line on the Evapo

Page 9

All installations and services must be performed by qualified service personnel. 16 5. A readily accessible, design-certified, manual oil shutoff va

Page 10

All installations and services must be performed by qualified service personnel. 17 and tank. This requires insertion of the "by-pass" plug

Page 11

All installations and services must be performed by qualified service personnel. 18 Table 2: Burner Specifications and High and Low Fire Heating Perf

Page 12

All installations and services must be performed by qualified service personnel. 1 Contents SECTION PAGE I. SAFETY INFORMATION ...

Page 13

All installations and services must be performed by qualified service personnel. 19 H. Airflow Requirements and Sizing of Duct Work The duct system

Page 14

All installations and services must be performed by qualified service personnel. 20 6. The following method can be used to size ductwork when air

Page 15

All installations and services must be performed by qualified service personnel. 21 h. The resistance of the take-off and the outlet register (or re

Page 16

All installations and services must be performed by qualified service personnel. 22 Table 3: Suggested Duct Sizes for Homes, Quiet Offices, Or Simila

Page 17

All installations and services must be performed by qualified service personnel. 23 8. As a final step in the installation, the appliance must be ad

Page 18

All installations and services must be performed by qualified service personnel. 24 J. Electrical Wiring : This appliance must be grounded in accor

Page 19

All installations and services must be performed by qualified service personnel. 25 Typically, control wiring between the outdoor appliance and the i

Page 20

All installations and services must be performed by qualified service personnel. 26 3. All wiring sizes must comply with local codes or the National

Page 21

All installations and services must be performed by qualified service personnel. 27 Figure 4: The Fan Control Module NOTICE: It is important

Page 22

All installations and services must be performed by qualified service personnel. 28 2. Thermostat Anticipator Setting Proper control of the indoor

Page 23

All installations and services must be performed by qualified service personnel. 2 Contents SECTION PAGE VI. DEALER MAINTENANCE ...

Page 24

All installations and services must be performed by qualified service personnel. 29 Preferred method of adjustment: Using an analog ammeter on the l

Page 25

All installations and services must be performed by qualified service personnel. 30 Or in this case, _2.5 A. = 0.25 A.

Page 26

All installations and services must be performed by qualified service personnel. 31 Figure 7: Blower Motor Terminal Blocks & Wiring

Page 27

All installations and services must be performed by qualified service personnel. 32 IV. STARTUP PROCEDURES A. Heating System 1. Initial Startup:

Page 28

All installations and services must be performed by qualified service personnel. 33 Operating Instructions: i. STOP! Read the s

Page 29

All installations and services must be performed by qualified service personnel. 34 ii. If service is to be performed, turn off the electrical powe

Page 30

All installations and services must be performed by qualified service personnel. 35 f. Open the inspection cover on the upper mounting plate above t

Page 31

All installations and services must be performed by qualified service personnel. 36 NOTICE: To achieve proper combustion and the efficiencies listed

Page 32

All installations and services must be performed by qualified service personnel. 37 The supply air temperature should be measured in the supply air t

Page 33

All installations and services must be performed by qualified service personnel. 38 b. Turn on the fuel oil and cause the appliance to activate the

Page 34

All installations and services must be performed by qualified service personnel. 3 I. SAFETY INFORMATION This page and the following page contain r

Page 35

All installations and services must be performed by qualified service personnel. 39 After 15 to 20 minutes of continuous operation, the temperature r

Page 36

All installations and services must be performed by qualified service personnel. 40 c. Make certain the thermostat will automatically start and stop

Page 37

All installations and services must be performed by qualified service personnel. 41 B. Cooling Section 1. Initial Startup: : Refrigerant is under p

Page 38

All installations and services must be performed by qualified service personnel. 42 pressure-temperature chart on the unit for approximate system lin

Page 39

All installations and services must be performed by qualified service personnel. 43 Startup of a new cooling system and checkout of an existing syst

Page 40

All installations and services must be performed by qualified service personnel. 44 Refer to Example 3, in Appendix B: Calculations of this manual, f

Page 41

All installations and services must be performed by qualified service personnel. 45 Once the liquid line pressure is known, the refrigerant temperatu

Page 42

All installations and services must be performed by qualified service personnel. 46 V. INSTALLER'S INSTRUCTIONS TO USER After completing the i

Page 43

All installations and services must be performed by qualified service personnel. 47 VI. DEALER MAINTENANCE SAFETY DURING SERVICING AND INSPECTION :

Page 44

All installations and services must be performed by qualified service personnel. 48 excessive wear. Replace it, if required. Check and adjust oil pum

Page 45

All installations and services must be performed by qualified service personnel. 4

Page 46

All installations and services must be performed by qualified service personnel. 49 Figure 9, OPA Heat Exchanger Clean-out Ports and Related Componen

Page 47

All installations and services must be performed by qualified service personnel. 50 With access to the inside of the heat exchanger through the burne

Page 48

All installations and services must be performed by qualified service personnel. 51 3. Operational Check : Before troubleshooting, familiari

Page 49

All installations and services must be performed by qualified service personnel. 52 D. Supply/Return Air Blower Check in the blower compartment for

Page 50

All installations and services must be performed by qualified service personnel. 53 NOTICE: Remind the homeowner of the importance of monthly filter

Page 51

All installations and services must be performed by qualified service personnel. 54 6. Open the inspection cover on the upper mounting plate. 7.

Page 52

All installations and services must be performed by qualified service personnel. 55 VII. HOMEOWNER/USER INFORMATION AND ROUTINE MAINTENANCE : Never

Page 53

All installations and services must be performed by qualified service personnel. 56 4. Check to see if the high temperature limit switch reset but

Page 54

All installations and services must be performed by qualified service personnel. 57 The following maintenance points should be reviewed periodicall

Page 55

All installations and services must be performed by qualified service personnel. 58 ducts for any signs of collapse, holes, or excessive corrosion. R

Page 56

All installations and services must be performed by qualified service personnel. 5 The following warnings and cautions are found throughout the Therm

Page 57

All installations and services must be performed by qualified service personnel. 59 VIII. TROUBLESHOOTING : Power must be disconnected before serv

Page 58

All installations and services must be performed by qualified service personnel. 60 The operational condition of the flame sensor, or “cad cell”, ca

Page 59

All installations and services must be performed by qualified service personnel. 61 1. Is the disconnect switch or the circuit breaker serving the a

Page 60

All installations and services must be performed by qualified service personnel. 62 IX. REFERENCES 1. International Approval Services-U.S. Inc. a

Page 61

All installations and services must be performed by qualified service personnel. 63 X. APPENDIX A: SOURCES FOR REFERENCED STANDARDS 1. Air Condit

Page 62

All installations and services must be performed by qualified service personnel. 64 XI. APPENDIX B: CALCULATIONS Example 1: Problem: It is desir

Page 63

All installations and services must be performed by qualified service personnel. 65 Figure 15: Plan View of a Typical Residence Solution: If certai

Page 64

All installations and services must be performed by qualified service personnel. 66 This procedure can be repeated to determine the airflow for each

Page 65

All installations and services must be performed by qualified service personnel. 67 Therefore, choose a supply system static pressure drop of 0.2 in.

Page 66 - RmLiving

All installations and services must be performed by qualified service personnel. 68 However, there are two, 90 degree turns in the branch that will c

Page 67

All installations and services must be performed by qualified service personnel. 6 : Waterproof type connectors must be used when connecting electric

Page 68

All installations and services must be performed by qualified service personnel. 69 For section “C”, including a 7-inch, 90-degree elbow, the pressur

Page 69

All installations and services must be performed by qualified service personnel. 70 Next, the branch of the system, which includes segments “D” and “

Page 70

All installations and services must be performed by qualified service personnel. 71 (),.10.50.90614.0392*75.485*00123174.02058.082.1ininDD≅=⎥⎦⎤⎢⎣⎡+=

Page 71

All installations and services must be performed by qualified service personnel. 72 Example 3: Problem: Refrigerant measurements are made on the c

Page 72

All installations and services must be performed by qualified service personnel. 73 Now, the degree of superheat can be calculated. 48°F (Su

Page 73 - °F. What is the

All installations and services must be performed by qualified service personnel. 74

Page 74

All installations and services must be performed by qualified service personnel. 75 XII. APPENDIX C: ELECTRICAL SCHEMATIC AND CONNECTION DIAGRAM

Page 75

All installations and services must be performed by qualified service personnel. 76 XIII. APPENDIX D: SEQUENCE OF OPERATIONS A. SEQUENCE OF OPERAT

Page 76

All installations and services must be performed by qualified service personnel. 77 Control System ActionMain Burner OperationMode of OperationCall

Page 77 - Control System Action

All installations and services must be performed by qualified service personnel. 78 XIV. APPENDIX E: TROUBLESHOOTING FLOWCHARTS TURN THERMOSTAT TO

Page 78

All installations and services must be performed by qualified service personnel. 7 : For initial start-up of the appliance after installation, it ma

Page 79

All installations and services must be performed by qualified service personnel. 79 BLOWER RUNSNORMAL CYCLE?IS IGNITION ESTABLISHED?FURNACE OPERATES

Page 80

All installations and services must be performed by qualified service personnel. 80 PROPER COMBUSTION ACHIEVED?NoNoNoIS PUMP PRESSURE SETACCORDING TO

Page 81

All installations and services must be performed by qualified service personnel. 81 IS THE TEMPERATUREDIFFERENCE BETWEEN SUPPLYIS STACK TEMPERATURED

Page 82

All installations and services must be performed by qualified service personnel. 82

Page 83

All installations and services must be performed by qualified service personnel. 83 Notes for Air Conditioning Troubleshooting Guide 1.101.0 Check

Page 84

All installations and services must be performed by qualified service personnel. 84 2.101.0 Check to see if the condenser fan motor is excessively h

Page 85

All installations and services must be performed by qualified service personnel. 85 3.101.1 Dirty air filters may restrict the airflow across the

Page 86

All installations and services must be performed by qualified service personnel. 86 XV. APPENDIX F: SPECIFICATION SHEETSModel No.:OPA24-80 OPA30-80

Page 87

All installations and services must be performed by qualified service personnel. 87 APPENDIX G: REPLACEMENT PARTS LIST

Page 88

All installations and services must be performed by qualified service personnel. 88

Page 89

All installations and services must be performed by qualified service personnel. 8 : Carefully read and thoroughly understand the following guideline

Page 90

All installations and services must be performed by qualified service personnel. 89 XVI. APPENDIX H: OPA HEATING AND COOLING SYSTEMS TEST FORM Nam