MO-425 ECN 4392-MA OIL FURNACE GENERAL SERVICE AND MAINTENANCE MANUAL FOR USE WITH THERMO PRIDE OIL FURNACES THERMO
All installations and services must be performed by qualified service personnel. 8 Fig. 8: Supply air duct sizing Example The RETURN AIR DUCT SYS
All installations and services must be performed by qualified service personnel. 9 D. OIL TANK & PIPING: ????WARNING: All local codes and ordin
All installations and services must be performed by qualified service personnel. 10 Below the wiring diagrams for the various Thermo Pride oil furnac
All installations and services must be performed by qualified service personnel. 11 G. INITIAL BURNER OPERATION: IMPORTANT: READ BURNER INSTRUCTION
All installations and services must be performed by qualified service personnel. 12 For example, if a 13% CO2 (3.5% O2) is measured at a trace of smo
All installations and services must be performed by qualified service personnel. 13 TURN T'STAT SETTINGABOVE ROOM TEMPERATURETURN THERMOSTAT TO
All installations and services must be performed by qualified service personnel. 14 POSITION THEM PERBURNER MANUFACTURERSINSTRUCTIONSREPLACE IGNITIO
All installations and services must be performed by qualified service personnel. 15 PROPER COMBUSTION ACHIEVED?IS THE PROBLEM DELAYEDIGNITION?IS PUM
All installations and services must be performed by qualified service personnel. 16 GO TO PROPER COMBUSTIONACHIEVED SECTION ABOVEAND SET COMBUSTIONA
All installations and services must be performed by qualified service personnel. 17 B. CAD CELL CHECKOUT PROCEDURE: 1. Remove cad cell lead wires,
All installations and services must be performed by qualified service personnel. i TABLE OF CONTENTS SECTION
All installations and services must be performed by qualified service personnel. 18 ????CAUTION: Do not attempt to start burner when: 1.Excess oil
All installations and services must be performed by qualified service personnel. 1 I. GENERAL INSTRUCTIONS - READ BEFORE START OF INSTALLATION 1. T
All installations and services must be performed by qualified service personnel. 2 If the "entire" building is unusually tightly constructe
All installations and services must be performed by qualified service personnel. 3 2. PREVENTION OF CHIMNEY CONDENSING: Stack gas may do one of two t
All installations and services must be performed by qualified service personnel. 4 3. PROPER CHIMNEY HEIGHT: The chimney shall terminate at least 3
All installations and services must be performed by qualified service personnel. 5 5. PROPER CHIMNEY BOTTOM LEVEL: In cases where the chimney extend
All installations and services must be performed by qualified service personnel. 6 Fig. 7: Alternate constructions that allow reduced clearances to
All installations and services must be performed by qualified service personnel. 7 The vent connector pipe between the furnace and chimney shall be o